Description

Currently, Ignition is designed to MAPO immediately based on a PG signal going away once 25ms has elapsed after the IBC is enabled.

This function might be better handled by the higher-level software on Sidecar/Scrimlet to determine what to do in case of a fault and it seems like it is safer if Ignition on each board only reports the faults up to software instead of taking autonomous action. If we get the autonomous action in Ignition wrong, it's a field service call to reprogram or replace hardware. If the action is controlled by a higher level software function, that behavior can be changed with a software update.