2ZoneDataCenterHVAC_wEconomizer performance discrepancies between 22-2-0 and 8-6-0

Open
#9,750 0 comments 0 reactions 0 assignees View on GitHub

Nobody has claimed this yet.

Dominant language
C++
Stars
1.6k
Forks
490
Avg merge
6d 21h
Merged PRs (30d)
22

Description

Issue overview

Run "energyplus -w USA_IL_Chicago-OHare.Intl.AP.725300_TMY3.epw -r -x -d output 2ZoneDataCenterHVAC_wEconomizer.idf"

The East Data Center results in very high temperatures, much higher than the cooling setpoint 23C. Some examples:

EAST ZONE:Zone Air Temperature [C](TimeStep)
45.4322699737891
46.6604832262426
47.2421209546278
47.4094961562255
47.413785803083
47.2434725514975
47.169790378188
EAST AIR LOOP OUTLET NODE:System Node Temperature [C](TimeStep)
40.3986960976602
41.2043134854439
41.464040595099
41.334086230615
41.0832801503033
41.0573809536309

Is this expected result - when the cooling setpoint is 23 C? Running the same simulation with version 8-6-0 gets seemingly reasonable results, where the temperatures were around 23C.

The West Data Center is OK.

Details

Some additional details for this issue (if relevant):

  • Platform: MacOS 10.15.7
  • Version of EnergyPlus 22-2-0, 22-1-0, 8-6-0
Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added (list location of defect file here)
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)

Contributor guide

Open the contributing guide

First steps

  1. Read the whole issue, then the project's contributing guide.
  2. Comment on the issue to say you are picking it up — it saves two people doing the same work.
  3. Fork the repository and make your change on a branch.
  4. Open a pull request that references the issue number.

Research direction

Reproduce the issue with the listed energyplus command, USA_IL_Chicago-OHare.Intl.AP.725300_TMY3.epw, and 2ZoneDataCenterHVAC_wEconomizer.idf under versions 22-2-0 and 8-6-0. Compare the East and West zone temperatures and air-loop outlet results. Done means determining whether the 22-2-0 discrepancy is expected and, if not, identifying the defect and updating the checklist items.

Written by the indexing model from the issue text.

Assessment

Tech stack
cpp
Domain
backend
Issue type
Bug
Difficulty
4/5
Estimated time
3-5 days
Activity status
Stale
Clarity
Mostly clear
Newbie friendliness
35/100

Get new issues in your inbox

A short digest of beginner-friendly GitHub issues.