ISISComputingGroup / ISISComputingGroup/IBEX
DETMON: current issues
- Dominant language
- No language data
- Stars
- 6
- Forks
- 2
- Avg merge
- 16h 40m
- Merged PRs (30d)
- 2
Description
The following need to be fixed
HVCAENA
There is a feature with the CAEN supplies that they need to have something read from them at least every 30 seconds or else they automatically disconnect the connection. The HVCAENA ioc connects to each CAEN in turn and dumps some information to a status file before starting normal EPICS polling, if the IOC is set to talk to too many crates then the connection to the first gets timed out before normal polling starts. This currently limits how many crates the IOC can be configured to talk to, and risks random failure of the ioc takes longer to start than expected
Runcontrol blocks long #5215
Contributor guide
No contributing guide indexed for this repository
Assessment
This issue has not been assessed yet.